EasyManua.ls Logo

GE 469

GE 469
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A: APPENDIX
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL A–3
Once again, if the polarity of one of the phases is out by 180°, the magnitude of the
resulting vector on a balanced system will be out by a factor of 1.73.
On a three wire supply, this configuration will always work and unbalance will be detected
properly. In the event of a single phase, there will always be a large unbalance present at
the interposing CTs of the relay. If for example Phase A was lost, Phase A would read zero
while Phase B and C would both read the magnitude of Phase C. If on the other hand,
phase B was lost, at the supply, Phase A would be 180° out-of-phase with Phase C and the
vector addition would equal zero at Phase B.

Table of Contents

Other manuals for GE 469

Related product manuals