Hydran* M2-X Installation Guide
MA-028 Rev. 2.1, 11-Jun-20
• Possible short-duration exposure: Oil up to 120 °C (248 °F)
• Vacuum-resistant sensor; 0–700 kPa (0–100 psia)
• Note: for units designated as Class I Div II Hazardous
Locations, working oil pressure 2 bar absolute (1 bar gauge)
• 100-120 Vac, 200-240 Vac, 50/60 Hz, 650 VA maximum
Meets standards EN 55022, IEC/EN 60255-22-1, IEC/EN 61000-3-
2, IEC/EN 61000-4-2, IEC/EN 61000-4-3, IEC/EN 61000-4-4,
IEC/EN 61000-4-5, IEC/EN 61000-4-6, IEC/EN 61000-4-8, IEC/EN
61000-4-1 1
Meets standards IEC 60068-2-1, IEC 60068-2-2, IEC 60068-2-6,
IEC 60068-2-30
Meets standard IEC 61010-1/EN 61010-1/UL61010-1/CSA C22.2
No.61010-1; HazLoc marked units UL120201 / CSA C22.2 No. 213
• Installed: 7.5 kg (16.5 lb)
• Shipping: 9 kg (20 lb)
Ambient temperature: -40 to +55 °C (-40 to +131 °F)
Relative humidity: 95 % RH, non-condensing
Altitude: up to 2,000 m (6,500 feet).
Temperature: +5 °C to +45 °C (+41 °F to +113 °F)
Storage period should not exceed 6 months.
Note: General Electric has made every reasonable attempt to ensure the completeness and
accuracy of these technical specifications. However, the information contained in these technical
specifications is subject to change without notice, and does not represent a commitment on the
part of General Electric.