Installing the Cables 
Figure 22: Removing the Hydran M2-X Cover 
  Installing the Cable Conduits and Gland Fittings 
GE Recommendations prior to installation: 
•All cables carrying; Power, Communications, analogue inputs and outputs, 
must be run in either rigid steel conduit or flexible steel liquid tight armoured 
conduit, with a minimum rating of IP56.  
•Using flexible steel armoured conduit makes it easier during installation and 
servicing of the Hydran M2-X.  
• All terminating connecting gland fittings to the Hydran M2-X must be liquid 
tight or at a minimum have an IP56 rating, with locknuts and sealing gaskets 
•The steel provides shielding against magnetic fields.