GE Multilin M60 Motor Protection System B-33
APPENDIX B B.4 MEMORY MAPPING
B
4E24 Raw Field Data Brick Rx Power 0 to 0.1 dBm 0.1 F002 0
4E25 Raw Field Data Brick Diagnostics (2 items) 0 to 65535 --- 1 F500 0
4E27 Raw Field Data Local Transceiver Temperature 0 to 1 degree 1 F002 0
4E28 Raw Field Data Local Transceiver Voltage 0 to 0.01 V 0.01 F001 0
4E29 Raw Field Data Local Transceiver Current 0 to 1 mA 1 F001 0
4E2A Raw Field Data Local Tx Power 0 to 0.1 dBm 0.1 F002 0
4E2B Raw Field Data Local Rx Power 0 to 0.1 dBm 0.1 F002 0
4E2C Repeated for module number 2
4E58 Repeated for module number 3
4E84 Repeated for module number 4
4E80 Repeated for module number 5
4EDC Repeated for module number 6
4F08 Repeated for module number 7
4F34 Repeated for module number 8
Flexlogic (Read/Write Setting)
5000 FlexLogic Entry (512 items) 0 to 4294967295 --- 1 F300 2097152
RTD Inputs (Read/Write Setting) (48 Modules)
5400 RTD Input 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5401 RTD Input 1 ID --- --- --- F205 “RTD Ip 1“
5407 RTD Input 1 Type 0 to 3 --- 1 F174 0 (100 ohm
Platinum)
5408 RTD Input 1 Application 0 to 5 --- 1 F550 0 (None)
5409 RTD Input 1 Alarm Temperature 1 to 249 °C 1 F001 130
540A RTD Input 1 Alarm Pickup Delay 0 to 600 s 0.01 F001 0
540B RTD Input 1 Trip Temperature 1 to 249 °C 1 F001 130
540C RTD Input 1 Trip Pickup Delay 0 to 600 s 0.01 F001 0
540D RTD Input 1 Trip Reset Delay 0 to 600 s 0.01 F001 0
540E RTD Input 1 Trip Voting 0 to 48 --- 1 F551 0
540F RTD Input 1 Open 0 to 2 --- 1 F552 0 (None)
5410 RTD Input 1 Block 0 to 4294967295 --- 1 F300 0
5412 RTD Input 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5413 RTD Input 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5414 ...Repeated for RTD Input 2
5428 ...Repeated for RTD Input 3
543C ...Repeated for RTD Input 4
5450 ...Repeated for RTD Input 5
5464 ...Repeated for RTD Input 6
5478 ...Repeated for RTD Input 7
548C ...Repeated for RTD Input 8
54A0 ...Repeated for RTD Input 9
54B4 ...Repeated for RTD Input 10
54C8 ...Repeated for RTD Input 11
54DC ...Repeated for RTD Input 12
54F0 ...Repeated for RTD Input 13
5404 ...Repeated for RTD Input 14
5518 ...Repeated for RTD Input 15
552C ...Repeated for RTD Input 16
5540 ...Repeated for RTD Input 17
5554 ...Repeated for RTD Input 18
5568 ...Repeated for RTD Input 19
557C ...Repeated for RTD Input 20
5590 ...Repeated for RTD Input 21
55A4 ...Repeated for RTD Input 22
55B8 ...Repeated for RTD Input 23
Table B–9: MODBUS MEMORY MAP (Sheet 26 of 66)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT