GE Multilin M60 Motor Protection System B-35
APPENDIX B B.4 MEMORY MAPPING
B
58C8 ...Repeated for FlexLogic Timer 26
58D0 ...Repeated for FlexLogic Timer 27
58D8 ...Repeated for FlexLogic Timer 28
58E0 ...Repeated for FlexLogic Timer 29
58E8 ...Repeated for FlexLogic Timer 30
58F0 ...Repeated for FlexLogic Timer 31
58F8 ...Repeated for FlexLogic Timer 32
Phase Instantaneous Overcurrent (Read/Write Grouped Setting) (up to 12 Modules)
5A00 Phase Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5A01 Phase Instantaneous Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5A02 Phase Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5A03 Phase Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5A04 Phase Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5A05 Phase IOC1 Block For Each Phase (3 items) 0 to 4294967295 --- 1 F300 0
5A0B Phase Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5A0C Phase Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5A0D Reserved (6 items) 0 to 1 --- 1 F001 0
5A13 ...Repeated for Phase Instantaneous Overcurrent 2
5A26 ...Repeated for Phase Instantaneous Overcurrent 3
5A39 ...Repeated for Phase Instantaneous Overcurrent 4
5A4C ...Repeated for Phase Instantaneous Overcurrent 5
5A5F ...Repeated for Phase Instantaneous Overcurrent 6
5A72 ...Repeated for Phase Instantaneous Overcurrent 7
5A85 ...Repeated for Phase Instantaneous Overcurrent 8
5A98 ...Repeated for Phase Instantaneous Overcurrent 9
5AAB ...Repeated for Phase Instantaneous Overcurrent 10
5ABE ...Repeated for Phase Instantaneous Overcurrent 11
5AD1 ...Repeated for Phase Instantaneous Overcurrent 12
Neutral Instantaneous Overcurrent (Read/Write Grouped Setting) (up to 12 Modules)
5C00 Neutral Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5C01 Neutral Instantaneous Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5C02 Neutral Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5C03 Neutral Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5C04 Neutral Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5C05 Neutral Instantaneous Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
5C07 Neutral Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5C08 Neutral Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5C09 Reserved (8 items) 0 to 1 --- 1 F001 0
5C11 ...Repeated for Neutral Instantaneous Overcurrent 2
5C22 ...Repeated for Neutral Instantaneous Overcurrent 3
5C33 ...Repeated for Neutral Instantaneous Overcurrent 4
5C44 ...Repeated for Neutral Instantaneous Overcurrent 5
5C55 ...Repeated for Neutral Instantaneous Overcurrent 6
5C66 ...Repeated for Neutral Instantaneous Overcurrent 7
5C77 ...Repeated for Neutral Instantaneous Overcurrent 8
5C88 ...Repeated for Neutral Instantaneous Overcurrent 9
5C99 ...Repeated for Neutral Instantaneous Overcurrent 10
5CAA ...Repeated for Neutral Instantaneous Overcurrent 11
5CBB ...Repeated for Neutral Instantaneous Overcurrent 12
Ground Time Overcurrent (Read/Write Grouped Setting) (up to 6 Modules)
5D00 Ground Time Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5D01 Ground Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5D02 Ground Time Overcurrent 1 Input 0 to 1 --- 1 F122 0 (Phasor)
5D03 Ground Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
Table B–9: MODBUS MEMORY MAP (Sheet 28 of 66)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT