B-36 M60 Motor Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
5D04 Ground Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod Inv)
5D05 Ground Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
5D06 Ground Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0 (Instantaneous)
5D07 Ground Time Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
5D09 Ground Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5D0A Ground Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5D0B Reserved (6 items) 0 to 1 --- 1 F001 0
5D11 ...Repeated for Ground Time Overcurrent 2
5D22 ...Repeated for Ground Time Overcurrent 3
5D33 ...Repeated for Ground Time Overcurrent 4
5D44 ...Repeated for Ground Time Overcurrent 5
5D55 ...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (up to 12 Modules)
5DA0 Ground Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5DA1 Ground Instantaneous Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5DA2 Ground Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5DA3 Ground Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5DA4 Ground Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5DA5 Ground Instantaneous Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
5DA7 Ground Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5DA8 Ground Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5DA9 Reserved (8 items) 0 to 1 --- 1 F001 0
5DB1 ...Repeated for Ground Instantaneous Overcurrent 2
5DC2 ...Repeated for Ground Instantaneous Overcurrent 3
5DD3 ...Repeated for Ground Instantaneous Overcurrent 4
5DE4 ...Repeated for Ground Instantaneous Overcurrent 5
5DF5 ...Repeated for Ground Instantaneous Overcurrent 6
5E06 ...Repeated for Ground Instantaneous Overcurrent 7
5E17 ...Repeated for Ground Instantaneous Overcurrent 8
5E28 ...Repeated for Ground Instantaneous Overcurrent 9
5E39 ...Repeated for Ground Instantaneous Overcurrent 10
5E4A ...Repeated for Ground Instantaneous Overcurrent 11
5E5B ...Repeated for Ground Instantaneous Overcurrent 12
CT Fail (Read/Write Setting) (6 Modules)
5E6C CT Fail 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5E6D CT Fail 1 Block 0 to 4294967295 --- 1 F300 0
5E6F CT Fail 1 Current Source 1 0 to 5 --- 1 F167 0 (SRC 1)
5E70 CT Fail 1 Current Pickup 1 0 to 2 pu 0.1 F001 2
5E71 CT Fail 1 Current Source 2 0 to 5 --- 1 F167 1 (SRC 2)
5E72 CT Fail 1 Current Pickup 2 0 to 2 pu 0.1 F001 2
5E73 CT Fail 1 Voltage Source 0 to 5 --- 1 F167 0 (SRC 1)
5E74 CT Fail 1 Voltage Pickup 0 to 2 pu 0.01 F001 20
5E75 CT Fail 1 Pickup Delay 0 to 65.535 s 0.001 F001 1000
5E76 CT Fail 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5E77 CT Fail 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5E78 ...Repeated for CT Fail 2
5E84 ...Repeated for CT Fail 3
5E90 ...Repeated for CT Fail 4
5E9C ...Repeated for CT Fail 5
5EA8 ...Repeated for CT Fail 6
Setting Groups (Read/Write Setting)
5F70 Setting Group for Modbus Comms (0 means group 1) 0 to 5 --- 1 F001 0
5F71 Setting Groups Block 0 to 4294967295 --- 1 F300 0
5F73 FlexLogic to Activate Groups 2 through 6 (5 items) 0 to 4294967295 --- 1 F300 0
Table B–9: MODBUS MEMORY MAP (Sheet 29 of 66)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT