B-38 M60 Motor Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
647D ...Repeated for Overfrequency 2
648A ...Repeated for Overfrequency 3
6497 ...Repeated for Overfrequency 4
Motor Setup (Read/Write Setting)
6600 Thermal Model Motor FLA 0.05 to 1 pu 0.001 F001 1000
6601 Thermal Model Motor Overload Factor 1 to 1.5 --- 0.01 F001 100
6602 Thermal Model Line Source 0 to 5 --- 1 F167 0 (SRC 1)
6603 Thermal Model Motor Offline 0 to 4294967295 --- 1 F300 0
6605 Thermal Model RTD 1 0 to 48 --- 1 F151 0 (NONE)
6606 Thermal Model RTD 2 0 to 48 --- 1 F151 0 (NONE)
6607 Thermal Model RTD 3 0 to 48 --- 1 F151 0 (NONE)
6608 Thermal Model RTD 4 0 to 48 --- 1 F151 0 (NONE)
6609 Thermal Model RTD 5 0 to 48 --- 1 F151 0 (NONE)
660A Thermal Model RTD 6 0 to 48 --- 1 F151 0 (NONE)
660B Motor Emergency Restart 0 to 4294967295 --- 1 F300 0
660D Motor Nameplate Voltage 100 to 50000 V 1 F001 600
660E Speed 2 Motor Protection 0 to 1 --- 1 F102 0 (Disabled)
660F Speed 2 Motor Switch 0 to 4294967295 --- 1 F300 0
6611 Speed 2 Switch 2-1 Delay 0 to 600 s 0.01 F001 500
6612 Speed 2 Motor Source 0 to 5 --- 1 F167 0 (SRC 1)
6613 Speed 2 Motor FLA 0.05 to 1 pu 0.001 F001 1000
Thermal Model Actuals (Read Only)
6630 Thermal Model Motor Status 0 to 3 --- 1 F098 1 (Starting)
6631 Thermal Model Capacity Used 0 to 100 % 1 F001 0
6633 Trip Time On Overload 0 to 10000 --- 1 F001 0
6634 Thermal Model Lockout Time 0 to 65000 min 1 F001 0
6638 Thermal Model Load 0 to 40 x FLA 0.01 F001 0
663A Thermal Model Motor Unbalance 0 to 100 % 1 F001 0
663B Thermal Model Biased Motor Load 0 to 40 x FLA 0.01 F001 0
663C Start/Hour Lockout Time 0 to 65000 min 1 F001 0
663D Time-Between-Starts Lockout Time 0 to 65000 min 1 F001 0
663E Restart Delay Lockout Time 0 to 50000 s 1 F001 0
663F Total Motor Lockout Time 0 to 65000 min 1 F001 0
Sensitive Directional Power (Read/Write Grouped Setting) (2 Modules)
6680 Sensitive Directional Power 1 Function 0 to 1 --- 1 F102 0 (Disabled)
6681 Sensitive Directional Power 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
6682 Sensitive Directional Power 1 RCA 0 to 359 degrees 1 F001 0
6683 Sensitive Directional Power 1 Calibration 0 to 0.95 degrees 0.05 F001 0
6684 Sensitive Directional Power 1 STG1 SMIN -1.2 to 1.2 pu 0.001 F002 100
6685 Sensitive Directional Power 1 STG1 Delay 0 to 600 s 0.01 F001 50
6686 Sensitive Directional Power 1 STG2 SMIN -1.2 to 1.2 pu 0.001 F002 100
6687 Sensitive Directional Power 1 STG2 Delay 0 to 600 s 0.01 F001 2000
6688 Sensitive Directional Power 1 Block 0 to 4294967295 --- --- F300 0
668A Sensitive Directional Power 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
668B Sensitive Directional Power 1 Events 0 to 1 --- 1 F102 0 (Disabled)
668C Reserved (5 items) 0 to 65535 --- 1 F001 0
6691 ...Repeated for Sensitive Directional Power 2
Underpower (Read/Write Grouped Setting) (2 Modules)
66AA Underpower 1 Function 0 to 1 --- 1 F102 0 (Disabled)
66AB Underpower 1 Start Block Delay 0 to 600 s 0.01 F001 50
66AC Underpower 1 Alarm Power Pickup 0.05 to 2 pu 0.01 F001 50
66AD Underpower 1 Alarm Pickup Delay 0 to 600 s 0.01 F001 200
66AE Underpower 1 Trip Power Pickup 0.05 to 2 pu 0.01 F001 40
66AF Underpower 1 Trip Pickup Delay 0 to 600 s 0.01 F001 100
Table B–9: MODBUS MEMORY MAP (Sheet 31 of 66)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT