GE Multilin M60 Motor Protection System B-39
APPENDIX B B.4 MEMORY MAPPING
B
66B0 Underpower 1 Trip Reset Delay 0 to 600 s 0.01 F001 100
66B1 Underpower 1 Block 0 to 4294967295 --- --- F300 0
66B3 Underpower 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
66B4 Underpower 1 Events 0 to 1 --- 1 F102 0 (Disabled)
66B5 ...Repeated for Underpower 2
Reduced Voltage Starting (Read/Write Grouped Setting)
6750 Reduced Voltage Start Function 0 to 1 --- 1 F102 0 (Disabled)
6751 Reduced Voltage Start Transition Mode 0 to 2 --- 1 F095 0 (Current Only)
6752 Reduced Voltage Start FLA 25 to 300 % 1 F001 125
6753 Reduced Voltage Start Timer 1.0 to 600.0 s 0.1 F001 100
6754 Reduced Voltage Start Block 0 to 4294967295 --- 1 F300 0
6755 Reduced Voltage Start Target 0 to 2 --- 1 F109 0 (Self-Reset)
6757 Reduced Voltage Start Event 0 to 1 --- 1 F102 0 (Disabled)
6758 Reserved (5 items) --- --- 1 F001 0
Motor Acceleration Actuals (Read Only Non-Volatile) (5 Modules)
68D0 Motor Acceleration 1 Time/Date 0 to 4294967295 --- 1 F050 0
68D2 Motor Acceleration 1 Starting Time 0 to 655.35 s 0.01 F001 0
68D3 Motor Acceleration 1 Effective Current 0 to 999999.999 A 0.001 F060 0
68D5 Motor Acceleration 1 Peak Current 0 to 999999.999 A 0.001 F060 0
68D7 Motor Acceleration 1 Reserved (9 items) --- --- --- F001 0
68DF ...Repeated for Motor Acceleration 2
68EE ...Repeated for Motor Acceleration 3
68FD ...Repeated for Motor Acceleration 4
690C ...Repeated for Motor Acceleration 5
Motor Acceleration Commands (Read/Write Command)
691F Motor Acceleration Clear Data Command 0 to 1 --- 1 F126 0 (No)
Motor Maximum Starting Rate (Read/Write Setting)
6920 Starts Per Hour Function 0 to 1 --- 1 F102 0 (Disabled)
6921 Starts Per Hour Time Interval 1 to 300 min 1 F001 60
6922 Starts Per Hour Maximum Number Of Starts 1 to 16 --- 1 F001 3
6923 Starts Per Hour Block 0 to 4294967295 --- 1 F300 0
6925 Starts Per Hour Target 0 to 2 --- 1 F109 0 (Self-reset)
6926 Starts Per Hour Events 0 to 1 --- 1 F102 0 (Disabled)
6927 Reserved (9 items) --- --- --- F001 0
Motor Time Between Starts (Read/Write Setting)
6930 Time Between Starts Function 0 to 1 --- 1 F102 0 (Disabled)
6931 Time Between Starts Minimum Time 0 to 300 min 1 F001 20
6932 Time Between Starts Block 0 to 4294967295 --- 1 F300 0
6934 Time Between Starts Target 0 to 2 --- 1 F109 0 (Self-reset)
6935 Time Between Starts Events 0 to 1 --- 1 F102 0 (Disabled)
6936 Reserved (10 items) 0 to 1 --- 1 F001 0
Motor Restart Delay (Read/Write Setting)
6940 Restart Delay Function 0 to 1 --- 1 F102 0 (Disabled)
6941 Restart Delay Minimum Time 0 to 50000 s 1 F001 0
6942 Restart Delay Block 0 to 4294967295 --- 1 F300 0
6944 Restart Delay Target 0 to 2 --- 1 F109 0 (Self-reset)
6945 Restart Delay Events 0 to 1 --- 1 F102 0 (Disabled)
6946 Reserved (10 items) --- --- --- F001 0
Motor Mechanical Jam (Read/Write Grouped Setting)
6950 Mechanical Jam Function 0 to 1 --- 1 F102 0 (Disabled)
6951 Mechanical Jam Pickup 1 to 10 x FLA 0.01 F001 200
6952 Mechanical Jam Pickup Delay 0.1 to 600 s 0.01 F001 10
6953 Mechanical Jam Reset Delay 0 to 600 s 0.01 F001 0
6954 Mechanical Jam Block 0 to 4294967295 --- 1 F300 0
Table B–9: MODBUS MEMORY MAP (Sheet 32 of 66)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT