B-40 M60 Motor Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
6956 Mechanical Jam Target 0 to 2 --- 1 F109 0 (Self-reset)
6957 Mechanical Jam Events 0 to 1 --- 1 F102 0 (Disabled)
6958 Reserved (8 items) --- --- --- F001 0
Motor Learned Data (Read/Write Setting)
6960 Motor Learned Data Starts to Learn 1 to 5 --- 1 F102 1
6961 Motor Learned Data Calculation Period 1 to 90 minutes 1 F001 15
6962 Reserved --- --- --- F001 0
Motor Learned Data (Read Only Actual Values)
6963 Motor Learned Data Records Number 0 to 250 --- 1 F001 0
6964 Motor Learned Data Last Cleared Date 0 to 4294967295 --- --- F050 0
6966 Motor Learned Data Acceleration Time 0 to 655.35 s 0.01 F001 0
6967 Motor Learned Data Starting Current 0.00 to 40.00 × FLA 0.01 F001 0
6968 Motor Learned Data Thermal Capacity Used 0 to 65535 % 1 F001 0
6969 Motor Learned Data Motor Load 0.00 to 40.00 × FLA 0.01 F001 0
696A Motor Learned Data Run Time After Start 0 to 4294967295 --- --- F050 0
696C Reserved --- --- --- F001 0
Phase Undervoltage (Read/Write Grouped Setting) (3 Modules)
7000 Phase Undervoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7001 Phase Undervoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7002 Phase Undervoltage 1 Pickup 0 to 3 pu 0.001 F001 1000
7003 Phase Undervoltage 1 Curve 0 to 1 --- 1 F111 0 (Definite Time)
7004 Phase Undervoltage 1 Delay 0 to 600 s 0.01 F001 100
7005 Phase Undervoltage 1 Minimum Voltage 0 to 3 pu 0.001 F001 100
7006 Phase Undervoltage 1 Block 0 to 4294967295 --- 1 F300 0
7008 Phase Undervoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7009 Phase Undervoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
700A Phase Undervoltage 1 Measurement Mode 0 to 1 --- 1 F186 0 (Phase to
Ground)
700B Reserved (6 items) 0 to 1 --- 1 F001 0
7011 ...Repeated for Phase Undervoltage 2
7022 ...Repeated for Phase Undervoltage 3
Phase Overvoltage (Read/Write Grouped Setting) (3 Modules)
7040 Phase Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7041 Phase Overvoltage 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7042 Phase Overvoltage 1 Pickup 0 to 3 pu 0.001 F001 1000
7043 Phase Overvoltage 1 Delay 0 to 600 s 0.01 F001 100
7044 Phase Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
7045 Phase Overvoltage 1 Block 0 to 4294967295 --- 1 F300 0
7047 Phase Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7048 Phase Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7049 ...Repeated for Phase Overvoltage 2
7052 ...Repeated for Phase Overvoltage 3
Phase Directional Overcurrent (Read/Write Grouped Setting) (2 Modules)
7200 Phase Directional Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7201 Phase Directional Overcurrent 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7202 Phase Directional Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
7204 Phase Directional Overcurrent 1 ECA 0 to 359 --- 1 F001 30
7205 Phase Directional Overcurrent 1 Pol V Threshold 0 to 3 pu 0.001 F001 700
7206 Phase Directional Overcurrent 1 Block Overcurrent 0 to 1 --- 1 F126 0 (No)
7207 Phase Directional Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7208 Phase Directional Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7209 Reserved (8 items) 0 to 1 --- 1 F001 0
7211 ...Repeated for Phase Directional Overcurrent 2
Table B–9: MODBUS MEMORY MAP (Sheet 33 of 66)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT