GE Multilin M60 Motor Protection System B-41
APPENDIX B B.4 MEMORY MAPPING
B
Neutral Directional Overcurrent (Read/Write Grouped Setting) (2 Modules)
7230 Neutral Directional Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7231 Neutral Directional Overcurrent 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7232 Neutral Directional Overcurrent 1 Polarizing 0 to 4 --- 1 F230 0 (Voltage)
7233 Neutral Directional Overcurrent 1 Forward ECA -90 to 90 ° Lag 1 F002 75
7234 Neutral Directional Overcurrent 1 Forward Limit Angle 40 to 90 degrees 1 F001 90
7235 Neutral Directional Overcurrent 1 Forward Pickup 0.006 to 30 pu 0.001 F001 50
7236 Neutral Directional Overcurrent 1 Reverse Limit Angle 40 to 90 degrees 1 F001 90
7237 Neutral Directional Overcurrent 1 Reverse Pickup 0.002 to 30 pu 0.001 F001 50
7238 Neutral Directional Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7239 Neutral Directional Overcurrent 1 Block 0 to 65535 --- 1 F300 0
723B Neutral Directional Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
723C Neutral Directional Overcurrent 1 Polarizing Voltage 0 to 1 --- 1 F231 0 (Calculated V0)
723D Neutral Directional Overcurrent 1 Op Current 0 to 1 --- 1 F196 0 (Calculated 3I0)
723E Neutral Directional Overcurrent 1 Offset 0 to 250 ohms 0.01 F001 0
723F Neutral Directional Overcurrent 1 Pos Seq Restraint 0 to 0.5 --- 0.001 F001 63
7240 Reserved 0 to 1 --- 1 F001 0
7241 ...Repeated for Neutral Directional Overcurrent 2
Disconnect (Breaker) Switch (Read/Write setting) (24 Modules)
74A0 Disconnect Switch 1 Function 0 to 1 --- 1 F102 0 (Disabled)
74A1 Disconnect Switch 1 Name --- --- --- F206 “SW 1"
74A4 Disconnect Switch 1 Mode 0 to 1 --- 1 F157 0 (3-Pole)
74A5 Disconnect Switch 1 Open 0 to 4294967295 --- 1 F300 0
74A7 Disconnect Switch 1 Block Open 0 to 4294967295 --- 1 F300 0
74A9 Disconnect Switch 1 Close 0 to 4294967295 --- 1 F300 0
74AB Disconnect Switch 1 Block Close 0 to 4294967295 --- 1 F300 0
74AD Disconnect Switch 1 Phase A / Three-pole Closed 0 to 4294967295 --- 1 F300 0
74AF Disconnect Switch 1 Phase A / Three-pole Opened 0 to 4294967295 --- 1 F300 0
74B1 Disconnect Switch 1 Phase B Closed 0 to 4294967295 --- 1 F300 0
74B3 Disconnect Switch 1 Phase B Opened 0 to 4294967295 --- 1 F300 0
74B5 Disconnect Switch 1 Phase C Closed 0 to 4294967295 --- 1 F300 0
74B7 Disconnect Switch 1 Phase C Opened 0 to 4294967295 --- 1 F300 0
74B9 Disconnect Switch 1 Operate Time 0 to 65.535 s 0.001 F001 70
74BA Disconnect Switch 1 Alarm Delay 0 to 65.535 s 0.001 F003 0
74BC Disconnect Switch 1 Events 0 to 1 --- 1 F102 0 (Disabled)
74BD Reserved (2 items) --- --- --- --- ---
74BF ...Repeated for module number 2
74DE ...Repeated for module number 3
74FD ...Repeated for module number 4
741C ...Repeated for module number 5
743B ...Repeated for module number 6
755A ...Repeated for module number 7
7579 ...Repeated for module number 8
7598 ...Repeated for module number 9
75B7 ...Repeated for module number 10
75D6 ...Repeated for module number 11
75F5 ...Repeated for module number 12
7614 ...Repeated for module number 13
7633 ...Repeated for module number 14
7652 ...Repeated for module number 15
7671 ...Repeated for module number 16
7690 ...Repeated for module number 17
76AF ...Repeated for module number 18
76CE ...Repeated for module number 19
Table B–9: MODBUS MEMORY MAP (Sheet 34 of 66)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT