B-44 M60 Motor Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
7D70 ...Repeated for User Programmable Pushbutton 12
7DA0 ...Repeated for User Programmable Pushbutton 13
7DD0 ...Repeated for User Programmable Pushbutton 14
7E00 ...Repeated for User Programmable Pushbutton 15
7E30 ...Repeated for User Programmable Pushbutton 16
Neutral Overvoltage (Read/Write Grouped Setting) (3 Modules)
7F00 Neutral Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7F01 Neutral Overvoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7F02 Neutral Overvoltage 1 Pickup 0 to 3.00 pu 0.001 F001 300
7F03 Neutral Overvoltage 1 Pickup Delay 0 to 600 s 0.01 F001 100
7F04 Neutral Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
7F05 Neutral Overvoltage 1 Block 0 to 4294967295 --- 1 F300 0
7F07 Neutral Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7F08 Neutral Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7F09 Neutral Overvoltage 1 Curves 0 to 3 --- 1 F116 0 (Definite Time)
7F0A Reserved (8 items) 0 to 65535 --- 1 F001 0
7F11 ...Repeated for Neutral Overvoltage 2
7F22 ...Repeated for Neutral Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting) (3 Modules)
7F60 Auxiliary Undervoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7F61 Auxiliary Undervoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7F62 Auxiliary Undervoltage 1 Pickup 0 to 3 pu 0.001 F001 700
7F63 Auxiliary Undervoltage 1 Delay 0 to 600 s 0.01 F001 100
7F64 Auxiliary Undervoltage 1 Curve 0 to 1 --- 1 F111 0 (Definite Time)
7F65 Auxiliary Undervoltage 1 Minimum Voltage 0 to 3 pu 0.001 F001 100
7F66 Auxiliary Undervoltage 1 Block 0 to 4294967295 --- 1 F300 0
7F68 Auxiliary Undervoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7F69 Auxiliary Undervoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7F6A Reserved (7 items) 0 to 65535 --- 1 F001 0
7F71 ...Repeated for Auxiliary Undervoltage 2
7F82 ...Repeated for Auxiliary Undervoltage 3
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 Modules)
7FA0 Auxiliary Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7FA1 Auxiliary Overvoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7FA2 Auxiliary Overvoltage 1 Pickup 0 to 3 pu 0.001 F001 300
7FA3 Auxiliary Overvoltage 1 Pickup Delay 0 to 600 s 0.01 F001 100
7FA4 Auxiliary Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
7FA5 Auxiliary Overvoltage 1 Block 0 to 4294967295 --- 1 F300 0
7FA7 Auxiliary Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7FA8 Auxiliary Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7FA9 Reserved (8 items) 0 to 65535 --- 1 F001 0
7FB1 ...Repeated for Auxiliary Overvoltage 2
7FC2 ...Repeated for Auxiliary Overvoltage 3
Frequency (Read Only)
8000 Tracking Frequency 2 to 90 Hz --- F001 0
Temp Monitor Actual Values (Read Only Non-Volatile)
81C0 Reserved Register T1 -55 to 125 C 1 F002 -55
81C1 Reserved Register T2 -55 to 125 C 1 F002 125
81C2 Reserved Register T3 -2147483647 to
2147483647
--- 1 F004 0
81C4 Reserved Register T4 0 to 4294967295 --- 1 F003 0
81C6 Reserved Register T5 0 to 4294967295 --- 1 F003 0
81C8 Reserved Register T6 0 to 4294967295 --- 1 F003 0
81CA Reserved Register T7 0 to 4294967295 --- 1 F003 0
Table B–9: MODBUS MEMORY MAP (Sheet 37 of 66)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT