GE Multilin M60 Motor Protection System B-51
APPENDIX B B.4 MEMORY MAPPING
B
9AA1 Teleprotection Channel 1 Number of Lost Packets 0 to 65535 --- 1 F001 0
9AA2 Teleprotection Channel 2 Status 0 to 2 --- 1 F134 1 (OK)
9AA3 Teleprotection Channel 2 Number of Lost Packets 0 to 65535 --- 1 F001 0
9AA4 Teleprotection Network Status 0 to 2 --- 1 F134 2 (n/a)
9AAF Teleprotection Channel 1 Input States 0 to 1 --- 1 F500 0
9AB0 Teleprotection Channel 2 Input States 0 to 1 --- 1 F500 0
9AC0 Teleprotection Input 1 States, 1 per register (16 items) 0 to 1 --- 1 F108 0 (Off)
9AD0 Teleprotection Input 2 States, 1 per register (16 items) 0 to 1 --- 1 F108 0 (Off)
Undercurrent (Read/Write Grouped Setting)
9F00 Undercurrent Function 0 to 1 --- 1 F102 0 (Disabled)
9F01 Undercurrent Speed 1 Start Block Delay 0.00 to 600.00 s 0.01 F001 50
9F02 Undercurrent Speed 1 Alarm Pickup 0.10 to 0.95 × FLA 0.01 F001 70
9F03 Undercurrent Speed 1 Alarm Pickup Delay 0.00 to 600.00 s 0.01 F001 200
9F04 Undercurrent Speed 1 Trip Pickup 0.10 to 0.95 × FLA 0.01 F001 70
9F05 Undercurrent Speed 1 Trip Pickup Delay 0.00 to 600.00 s 0.01 F001 100
9F06 Undercurrent Speed 1 Trip Reset Delay 0.00 to 600.00 s 0.01 F001 100
9F07 Undercurrent Speed 1 Block 0 to 4294967295 --- 1 F300 0
9F08 Undercurrent Target 0 to 2 --- 1 F109 0 (Self-reset)
9F09 Undercurrent Events 0 to 1 --- 1 F102 0 (Disabled)
9F0A Undercurrent Speed 2 Start Block Delay 0.00 to 600.00 s 0.01 F001 50
9F0B Undercurrent Speed 2 Alarm Pickup 0.10 to 0.95 × FLA 0.01 F001 70
9F0C Undercurrent Speed 2 Alarm Pickup Delay 0.00 to 600.00 s 0.01 F001 200
9F0D Undercurrent Speed 2 Trip Pickup 0.10 to 0.95 × FLA 0.01 F001 70
9F0E Undercurrent Speed 2 Trip Pickup Delay 0.00 to 600.00 s 0.01 F001 100
9F0F Undercurrent Speed 2 Trip Reset Delay 0.00 to 600.00 s 0.01 F001 100
9F10 Undercurrent Speed 2 Block 0 to 4294967295 --- 1 F300 0
9F11 Reserved (2 items) --- --- --- F001 0
Broken Rotor Bar Detection (Read Only Actual Values)
A020 Broken rotor bar component level –100 to 0 dB 0.1 F002 –1000
A021 Broken rotor bar component frequency 0 to 76 Hz 0.01 F001 0
A022 Motor load at broken rotor bar calculation 0 to 1.5 × FLA 0.01 F001 0
A023 Motor load deviation at broken rotor bar calculation 0 to 1.5 × FLA 0.01 F001 0
A024 Time stamp at broken rotor bar calculation 0 to 4294967295 --- 1 F050 0
A026 Maximum broken rotor bar component level –100 to 0 dB 0.1 F002 –1000
A027 Maximum broken rotor bar component frequency 0 to 76 Hz 0.01 F001 0
A028 Motor load at broken rotor bar maximum 0 to 1.5 × FLA 0.01 F001 0
A029 Motor load deviation at broken rotor bar maximum 0 to 1.5 × FLA 0.01 F001 0
A02A Time stamp at broken rotor bar maximum 0 to 4294967295 --- 1 F050 0
Broken Rotor Bar Commands (Read/Write Commands)
A02D Broken rotor bar clear data command 0 to 1 --- 1 F126 0 (No)
Broken Rotor Bar Detection (Read/Write Settings)
A030 Broken rotor bar function 0 to 1 --- 1 F102 0 (Disabled)
A031 Start of broken rotor bar offset –12 to 11.99 Hz 0.01 F002 40
A032 End of broken rotor bar offset –11.99 to 12 Hz 0.01 F002 200
A033 Broken rotor bar start block delay 0 to 600 s 0.01 F001 6000
A034 Minimum motor load 0.5 to 1 × FLA 0.01 F001 70
A035 Maximum load deviation 0 to 1 × FLA 0.01 F001 10
A036 Maximum current unbalance 0 to 100 % 0.1 F001 150
A037 Broken rotor bar pickup –60 to –12 dB 1 F002 -40
A038 Broken rotor bar reset delay 0 to 600 s 0.01 F001 0
A039 Broken rotor bar block 0 to 4294967295 --- 1 F300 0
A03B Broken rotor bar target 0 to 2 --- 1 F109 0 (Self-reset)
A03C Broken rotor bar events 0 to 1 --- 1 F102 0 (Disabled)
Table B–9: MODBUS MEMORY MAP (Sheet 44 of 66)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT