20 MM200 MOTOR MANAGEMENT SYSTEM – QUICK START GUIDE
CONFIGURATION SETPOINTS CHAPTER 3: SETPOINTS
CT Primary (Mandatory setpoint)
Range: 5 to 1000 amps in steps of 1
Default: 5 amps
This setpoint specifies the phase CT primary current. It should never be less than the full
load current, and preferably no greater than twice than the full load current.
NOTE
NOTE:
This setpoint is displayed only if the phase CT is selected to 1 A secondary or 5 A
secondary.
High Speed CT Primary
Range: 5 to 1000 amps in steps of 1
Default: 5 amps
This setpoint specifies the phase CT primary current when the motor is running at high
speed. It should never be less than the high speed full load current, and preferably no
greater than twice than the high speed full load current.
NOTE
NOTE:
This setpoint is displayed only if the phase CT is selected as 1 A secondary or 5 A secondary
and the motor starter type is two-speed.