EasyManuals Logo

GE MM200 Quick Start Guide

GE MM200
45 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #33 background imageLoading...
Page #33 background image
28 MM200 MOTOR MANAGEMENT SYSTEM – QUICK START GUIDE
USER INTERFACE SPECIFICATIONS CHAPTER 6: SPECIFICATIONS
GROUND FAULT (CBCT)
Pickup level:........................................................... 0.5 to 15.0 A in steps of 0.1 A
Trip time delay on start:................................... 0 to 10 s in steps of 0.1 s
Trip time delay on run: ..................................... 0 to 5 s in steps of 0.1 s
Alarm time delay on start/run:..................... 0 to 60 s in steps of 1 s
Timing accuracy: ................................................ ±100 ms or ±0.5% of total time
Elements:................................................................ trip and alarm
LOAD INCREASE
Pickup level:........................................................... 50 to 150% of FLA in steps of 1%
Timing accuracy: ................................................ ±500 ms
Elements:................................................................ Alarm
MECHANICAL JAM
Pickup level:........................................................... 1.01 to 4.50 × FLA in steps of 0.01
Time delay: ............................................................ 0.1 to 30.0 seconds in steps of 0.1
Timing accuracy: ................................................ ±500 ms
Elements:................................................................ trip
THERMAL MODEL
Standard curve time multiplier: ................... 1 to 15 in steps of 1
Thermal overload pickup:............................... 1.01 to 1.25 in steps of 0.01 x FLA
Motor full load current (FLA): ......................... 0.5 to 1000 A in steps of 0.1
Motor rated voltage: ......................................... 100 to 690 V AC
Curve biasing:....................................................... hot/cold ratio exponential running and stopped cooling
rates
Update rate:.......................................................... 3 cycles
Hot/cold safe stall ratio:.................................. 1 to 100% in steps of 1%
Timing accuracy: ................................................ ±200 ms or ±2% of total time (based on measured value)
Elements:................................................................ trip
THERMISTOR
Sensor types: ........................................................ PTC (R
HOT
= 100 to 30 kohms); NTC (R
HOT
= 100 to 30 kohms)
Timing accuracy: ................................................ ±500 ms
Elements:................................................................ Trip and alarm
UNDERCURRENT
Pickup level:........................................................... 1 to 100% of FLA in steps of 1
Time delay: ............................................................ 1 to 60 seconds in steps of 1
Timing accuracy: ................................................ ±500 ms
Elements:................................................................ Trip and alarm
POWER FAILURE RESTART
Type: ......................................................................... Digital input
Power failure time:............................................. 0 to 30 seconds in steps of 1
Restart time delay:............................................. 0 to 300 seconds in steps of 1
UV detection time accuracy:......................... ±100 ms or ±5%
User interface specifications
HAND HELD DISPLAY (HHD)
Size: ........................................................................... width 153mm, height 102mm, depth 35mm
LCD:........................................................................... 3.5-inch color, 320 by 240 pixels
LED Indicators:..................................................... 10 LEDs
Pushbuttons:......................................................... Start A, Start B, Stop, plus 11 LCD screen display control keys
Ports:......................................................................... USB 2.0 port for laptop computer connection
Cable - GCP to Base Unit: ............................... Shielded RJ45; Maximum length 6' (1.83m)