CHAPTER 6: SPECIFICATIONS TESTING AND CERTIFICATION
MM200 MOTOR MANAGEMENT SYSTEM – QUICK START GUIDE 31
RS485 PORT
Port: ........................................................................... opto-isolated
Baud rates:............................................................. up to 115 kbps
Protocol: .................................................................. Modbus RTU, half-duplex
Maximum distance: ........................................... 1200 m
Isolation:.................................................................. 2 kV
Testing and certification
TYPE TESTS (TEST NOT PERFORMED FOR AC PSU)
Test Reference Standard Test Level
Dielectric voltage withstand 2.3KV
Impulse voltage withstand EN60255-5 5KV
Damped Oscillatory IEC61000-4-18IEC60255-22-1 2.5KV CM, 1KV DM
Electrostatic Discharge EN61000-4-2/IEC60255-22-2 Level 4
RF immunity EN61000-4-3/IEC60255-22-3 Level 3
Fast Transient Disturbance EN61000-4-4/IEC60255-22-4 Class A
Surge Immunity EN61000-4-5/IEC60255-22-5 Level 3
Conducted RF Immunity EN61000-4-6/IEC60255-22-6 Level 3
Power Frequency Immunity EN61000-4-7/IEC60255-22-7 Class A
Voltage interruptionand Ripple DC IEC60255-11 15% ripple, 200ms interupts
Radiated & Conducted Emissions CISPR11 /CISPR22/ IEC60255-25 Class A
Sinusoidal Vibration IEC60255-21-1 Class 1
Shock & Bump IEC60255-21-2 Class 1
Siesmic IEC60255-21-3 Class 2
Power magnetic Immunity IEC61000-4-8 Level 5
Pulse Magnetic Immunity IEC61000-4-9 Level 4
Damped Magnetic Immunity IEC61000-4-10 Level 4
Voltage Dip & interruption IEC61000-4-11 0,40,70% dips,250/300cycle
interrupts
Damped Oscillatory IEC61000-4-12 2.5KV CM, 1KV DM
Voltage Ripple IEC61000-4-17 15% ripple
Ingress Protection IEC60529 IP20 (base unit) , IP54
(Control Panel)
Environmental (Cold) IEC60068-2-1 -25C 16 hrs
Environmental (Dry heat) IEC60068-2-2 70C 16hrs
Relative Humidity Cyclic IEC60068-2-30 6day variant 2
UL508 e83849 NKCR
Safety UL C22.2-14 e83849 NKCR7
UL1053 e83849 NKCR