P54A/B/C/E
Appendix B - Settings and Signals
P54xMED-TM-EN-1
B201
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
Setting that determines impact of the second stage sensitive earth fault overcurrent protection on AR operation.
ISEF>3 AR 49 86 No Action
No Action
Initiate AR
Block AR
[Indexed String]
Setting that determines impact of the third stage sensitive earth fault overcurrent protection on AR operation.
ISEF>4 AR 49 87 No Action
No Action
Initiate AR
Block AR
[Indexed String]
Setting that determines impact of the fourth stage sensitive earth fault overcurrent protection on AR operation.
Neutral Diff AR 49 88 Initiate AR
Initiate AR
Block AR
[Indexed String]
Setting that determines impact of the Neutral Differential protection on AR operation.
AR SYS CHECKS
49
A5
System Checks Sub Heading
CB SC all 49 A6 Disabled
Disabled
Enabled
[Indexed String]
This setting determines whether a system check (e.g. live bus / dead line etc) is required for any auto-reclose of CB. If Enabled, system check
is required for some or all reclosures. If Disabled, system check is not required for any reclosures.
CB1L SC all 49 A6 Disabled
Disabled
Enabled
[Indexed String]
This setting determines whether a system check (e.g. live bus / dead line etc) is required for any auto-reclose of CB1 as leader. If Enabled,
system check is required for some or all reclosures. If Disabled, system check is not required for any reclosures.
CB SC Shot 1 49 A7 Disabled
Disabled
Enabled
[Indexed String]
This setting determines whether a system check (e.g. live bus / dead line etc) is required for the first shot reclosure of CB. If Enabled, system
check is required for the first shot reclosure. If Disabled, system check is not required for the first shot reclosure.
CB1L SC Shot 1 49 A7 Disabled
Disabled
Enabled
[Indexed String]
This setting determines whether a system check (e.g. live bus / dead line etc) is required for the first shot reclosure of CB1 as leader. If
Enabled, system check is required for the first shot reclosure. If Disabled, system check is not required for the first shot reclosure.
CB SC ClsNoDly 49 A8 Disabled
Disabled
Enabled
[Indexed String]
If CB SC ClsNoDly is Enabled, CB can reclose as leader as soon as the synchro check conditions are satisfied, without waiting for the dead
time to elapse.
This option is sometimes required for the second line end to reclose onto a line with delayed auto-reclosing (typical cycle: first line end
recloses after the dead time with
live bus & dead line, then the second line end recloses immediately with live bus & live line in synchronism).
CB1L SC ClsNoDly 49 A8 Disabled
Disabled
Enabled
[Indexed String]
If CB1L SC ClsNoDly is Enabled, CB1 can reclose as leader as soon as the synchro check conditions are satisfied, without waiting for the dead
time to elapse.
This option is sometimes required for the second line end to reclose onto a line with delayed auto-reclosing (typical cycle: first line end
recloses after the dead time with
live bus & dead line, then the second line end recloses immediately with live bus & live line in synchronism).
CB SC CS1 49 A9 Disabled
Disabled
Enabled
[Indexed String]
This setting enables CB to auto-reclose as leader when the system satisfies all the System Check Synchronism Stage 1 criteria as defined
under CB CS1 Status settings in the SYSTEM CHECKS column.
CB1L SC CS1 49 A9 Disabled
Disabled
Enabled
[Indexed String]