CHAPTER 5: SETPOINTS
PQMII POWER QUALITY METER – INSTRUCTION MANUAL 5–23
Table 5–4: Analog Output Parameters (Sheet 1 of 2)
Parameter Range Step
Phase A Current 0 to 150% 1%
Phase B Current 0 to 150% 1%
Phase C Current 0 to 150% 1%
Neutral Current 0 to 150% 1%
Average Phase Current 0 to 150% 1%
Current Unbalance 0 to 100.0% 0.1%
Voltage Van 0 to 200% 1%
Voltage Vbn 0 to 200% 1%
Voltage Vcn 0 to 200% 1%
Voltage Vab 0 to 200% 1%
Voltage Vbc 0 to 200% 1%
Voltage Vca 0 to 200% 1%
Average Phase Voltage 0 to 200% 1%
Average Line Voltage 0 to 200% 1%
Voltage Unbalance 0 to 100.0% 0.1%
Frequency 00.00 to 75.00 Hz 0.01 Hz
3 Phase PF 0.01 lead to 0.01 lag 0.01
3 Phase kW –32500 to +32500 1 kW
3 Phase kvar –32500 to +32500 1 kvar
3 Phase kVA 0 to 65400 1 kVA
3 Phase MW –3250.0 to +3250.0 0.1 MW
3 Phase Mvar –3250.0 to +3250.0 0.1 Mvar
3 Phase MVA 0 to 6540.0 0.1 MVA
Phase A PF 0.01 lead to 0.01 lag 0.01
Phase A kW –32500 to +32500 1 kW
Phase A kvar –32500 to +32500 1 kvar
Phase A kVA 0 to 65400 1 kVA
Phase B PF 0.01 lead to 0.01 lag 0.01
Phase B kW –32500 to +32500 1 kW
Phase B kvar –32500 to +32500 1 kvar