EasyManua.ls Logo

GE RX3i - Page 98

GE RX3i
276 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 5. Ethernet Global Data
GFK-2224Q January 2017 85
Command Block for Enable/Disable PLC Time Update COMMREQ
Word Offset Value Description
Word 1 Length of command data block. Always 2
Word 2 0 Always 0 (Wait/No Wait mode request).
Word 3 For a list of memory type codes, see
“COMMREQ Status for the EGD
Commands” in Chapter 6.
Memory type of the COMMREQ status word.
Word 4 0-based Offset of COMMREQ status word. For CRS word
values, refer to page 86.
Word 5 0 Always 0.
Word 6 0 Always 0.
Word 7 5002 Enable/Disable Time Update command number
Word 8 1 = Enable PLC time update
0 = Disable PLC time update
This word contains the value to enable or disable
this Ethernet interface to update the PLC clock. This
word must be set to 0 to disable PLC clock updates,
and set to 1 to enable PLC clock updates. All other
values will cause COMMREQ to return a failure
status.

Table of Contents

Related product manuals