Mechanical Separation / GEA Westfalia Separator
4.5 Alarm #07 - Ejection monitoring
Eject. curr.< offset
Separation “Stop”
Alarm#07 ENTER
Textdisplay Possible causes Action
Operating water valve V3 is defective.
• Check bowl hydraulic function with
operating water valve V3.
Connector on operating water valve V3
is loose.
• Check connector on operating
water valve V3.
Offset setting for ejection current ad-
justed too high.
• Check offset setting.
Water volume at V3 too low.
•
Check water volume.
Monitoring time T28 too short.
•
Check T28.
Current evaluation defective.
• Check current transformer electri-
callly.
Filter insert in strainer at solenoid block
soiled.
• Check filter insert.
Clutch shoes worn or oily.
•
Check clutch shoes.
Help text – Information on the control system
ENT E R
Step 1 Acknowledge fault.
HEL P
Step 2
Press key >F1<
Help on alarm
Key >HOME< back
Page 1
EJECTION MONITORING
Please check:
Bowl function
Hydraulic with V3
->
Seite 2
Plug-in valvel V3
Current offset
Setting
Water volume
->
Page 3
T28
Current transformer electr.
Prestrainer
Back with ENTER
F1