140 ADV200 • Functions description and parameters list
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.16.1 3500Drvtempsrc LINK 32BIT 6000 0 16384 ERW FVS
Selection of signal origin (source) for management of a temperature signal. The parameter to be assigned to
this function is selected from the “L_TEMPCTRL” selection list.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.16.2 3504Drvtempthr degC INT32 45 1 100 ERW FVS
Setting of trip threshold for an alarm signal.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.16.3 3508Drvtemphys degC INT32 2 0 CALCI ERW FVS
Setting of a tolerance band for the trip threshold set in PAR 3504.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.16.4 3502Mottempsrc LINK 32BIT 6000 0 16384 ERW FVS
Selection of signal origin (source) for management of a temperature signal. The parameter to be assigned to
this function is selected from the “L_TEMPCTRL” selection list.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.16.5 3506Mottempthr degC INT32 45 1 100 ERW FVS
Setting of trip threshold for an alarm signal.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.16.6 3510Mottemphys degC INT32 2 0 CALCI ERW FVS
Setting of a tolerance band for the trip threshold set in PAR 3506.