AGy-EV Instruction manual Chapter 7 - Parameters Description • 105
7.3 Menu S - START-UP
NOTE! The START UP menu is a set of parameters and functions that allows a quick start of the motor.These
parameters are actually links to a selection of parameters present in other menus. Therefore, avy
modification on a parameter in the START-UP menu is also reflected on the linked parameter found on
a different menu, and vice-versa.
Power Supply
S.000 Mains voltage (linked to P.020)
Rated value of the AC input mains line to line voltage [V].
The undervoltage trip function is based on this value (see chapter PARAMETERS, section Undervoltage
configuration).
S.001 Mains frequency (linked to P.021)
Rated value of the AC input mains frequency [Hz].
Code LCD display [Code] & LCD select. Default MIN MAX Unit Variation IPA
S.000 Mains voltage - 230, 380, 400, 420, 440, 460, 480 (****) 230 575 V 404
(Only for "AGy...-4")
- 500, 575 (Only for "AGy...-5")
S.001 Mains frequency 50 (****) 50 60 Hz 405
60
(****) parameter value dependent on drive type.
V/F Characteristic
S.100 Max out voltage (Maximun output voltage) (linked to P.061)
Maximum value of the voltage applied to the motor (normally set as the nameplate, see figure 7.3.2).
S.101 Base frequency (linked to P.062)
Rated frequency of the motor (given on the nameplate, see figure 7.3.2)
It is the frequency at which the inverter output voltage reaches the Max out voltage (S.100).
S.100
(S.101)
(S.201)
F
(n)
V
S.100
S.101
S.201
F
(n)
V
Figure 7.3.1: V/F Characteristic
NOTE! For further setting of the V/F characteristic, see the chapter PARAMETERS, section V/F Curve
Code LCD display [Code] & LCD select. Default MIN MAX Unit Variation IPA
S.100 Max out voltage (**) 50 (**) V 1 413
S.101 Base frequency (**) 25 500 Hz 0,1 414
(**) parameter value dependent on drive nominal mains voltage and mains frequency.