AGy-EV Instruction manual Chapter 7 - Parameters Description • 175
100%
V
t
F
t
Ramp Profile
P.421
Figure 7.6.21: Output Voltage Reduction with P.420 = 1
NOTE! the function can be enabled also through the digital inputs (see chapter INTERFACE, section Digital
inputs). In this case it will be possible to enable the Output Voltage reduction at any time the command
is applied.
Code LCD display [Code] & LCD select. Default MIN MAX Unit Variation IPA
P.420 Volt reduc mode [0] Always 0 0 1 471
[1] Steady state
P.421 V reduction fact 100 10 100 % of P.061 1 472
P.422 V fact mult src [0] Null 0 0 3 473
[1] Analog inp 1 (setting through I.200…I.204)
[2] Analog inp 2 (setting through I.210…I.214)
[3] Analog inp 3 (setting through I.220…I.224)
Frequency Threshold
P.440 Frequency prog 1 (Frequency programmed 1)
Set point for the detection of the first frequency threshold.
The signalling of the frequency level detection can be programmed on the digital outputs.
P.441 Freq prog 1 hyst (Frequency programmed 1 hysteresis)
Defines a tolerance band around the Frequency prog 1 (P.440).
P.442 Frequency prog 2 (Frequency programmed 2)
Set point for the detection of the second frequency threshold.
The signalling of the frequency level detection can be programmed on the digital outputs.
P.443 Freq prog 2 hyst (Frequency programmed 2 hysteresis)
Defines a tolerance band around the Frequency prog 2 (P.442).