16 • Chapter 3 Inspection Procedure, Component Identification and Standard Specification AGy-EV Instruction manual
3.3 Standard Specifications
3.3.1 Permissible Environmental Conditions
Table 3.3.1.1: Environmental Specification
[°C] 0 +40; +40…+50 with derating
[°F] 32 +104; +104…+122 with derating
Installation location
Installation altitude
Temperature:
operation
1)
operation
2)
storage
transport
Air humidity:
operation
storage
transport
Air pressure:
operation [kPa] 86 to 106 (class 3K3 as per EN50178)
storage [kPa] 86 to 106 (class 1K4 as per EN50178)
transport [kPa] 70 to 106 (class 2K3 as per EN50178)
General standards
Safety
Climatic conditions
Clearance and creepage
Vibration
EMC compatibility
Rated input voltages
Approvals
TGy0020
-20…+60°C (-4…+140°F), for devices with keypad
IP20 according to EN 60529
IP54 for the cabinet with externally mounted heatsink; only for sizes from 1007 to 3150 (230V…480V) and
from 2002 to 3020 (575V)
EN 50178, UL508C, UL840. Overvoltage category for mains connected circuits: III; degree of pollution 2
EN 60068-2-6, test Fc.
-20…+55°C (-4…+131°F), for devices with keypad
CE, UL, cUL, CSA
ENVIRONMENT
STANDARD
Pollution degree 2 or better (free from direct sunligth, vibration, dust, corrosive or inflammable gases, fog,
vapour oil and dripped water, avoid saline environment)
Up to 1000m (3281 feet) above sea level; for higher altitudes a current reduction of 1.2% for every 100m (328
feet) of additional height applies .
A light condensation of moisture may occur for a short time occasionally if the device is not in operation (class 2K3 as per
EN50178)
EN61800-3/A11 (see “EMC Guidelines” instruction book)
IEC 60038
-25…+70°C (-13…+158°F), class 2K3 per EN50178
T
A
Ambient temperature
0…40°C (32°…104°F)
0…50°C (32°…122°F)
-25…+55°C (-13…+131°F), class 1K4 per EN50178
Protection degree
95 %
3)
60 g/m
4)
EN 61800-1, IEC 143-1-1.
5%to85%,1g/m
3
to 25 g/m
3
without moisture condensation or icing (Class 3K3 as per EN50178)
5% to 95 %, 1 g/m
3
to 29 g/m
3
(Class 1K3 as per EN50178)
EN 50178, UL 508C
EN 60721-3-3, class 3K3. EN 60068-2-2, test Bd.
1)
Over 40°C (104°F):
- current reduction of 2% of rated output current per K
- remove front plate (better than class 3K3 as per EN50178)
2)
Current derated to 0.8 rated ouput current
Over 40°C (104°F): removal of the top cover (better than class 3K3 as per EN50178)
3)
Greatest relative air humidity occurs with the temperature @ 40°C (104°F) or if the temperature of the device is
brought suddenly from -25 ...+30°C (-13°...+86°F).
4)
Greatest absolute air humidity if the device is brought suddenly from 70...15°C (158°...59°F).