10 • Chapter 1 - Safety AGy-EV Instruction manual
1.1 Power Supply and Grounding
1) GEFRAN drives are designed to be powered from standard three phase lines that are electrically symmetrical
with respect to ground (TN or TT network).
Les variateurs GEFRAN sont prévus pour être alimentés par un réseau triphasé équilibré avec un régime de neutre
standard (TN ou TT).
2) In case of supply with IT network, the use of delta/wye transformer is mandatory, with a secondary three phase
wiring referred to ground.
Si le régime de neutre est IT, nous vous recommendons d'utiliser un tranformateur triangle/étoile avec point milieu
ramené à la terre.
In case of a three phase supply not symmetrical to ground, an insulation loss of one of the devices
connected to the same network can cause functional problem to the drive, if the use of a delta/wye
transformer is avoided.
Si le réseau n'est pas équilibré par rapport à la terre et qu'il n'y a pas de transformateur raingle/étoile,
une mauvaise isolation d'un appareil électrique connecté au même réseau que le variateur peut lui
causer des troubles de fonctionnement.
Please refer to the following connection sample.
Safety
ground
L1
L2
L3
Earth
U1/L1
V1/L2
W1/L3
U2/T1
V2/T2
W2/T3
PE2/
All wires (including motor ground) must
be connected inside the motor terminal box
AC OUTPUT
CHOKE
AC Main Supply
AC INPUT
CHOKE
PE1/
Warning!