16 / 40
3030
mFlow
Configuration level Display Function Value range Factory setting
3 SetFunction
Analog Output
Submenu for setting the analogue outputs
Q min
Flow rate value, for which 4
mA is output
0 to 90,000,000 l/h
Q max
Flow rate value, for which 20
mA is output
0 to 90,000,000 l/h
Digital Output
Submenu for setting the digital outputs
K1 Switch Defines the type of output NC / NO NO
K1 Fn
Determines the function of
output K1
OFF
Q min
Q max
Q min/max
T min
T max
T min / max
TQ1 min
TQ1 max
TQ1 min / max
TQ2 min
TQ2 max
TQ2 min / max
Direction
Warning
OFF
AlarmMinK1 Value for the min. alarm K1
± 90,000,000 l/h /
0 to 100 °C
0 l/h /
0 °C
AlarmMaxK1 Value for the max. alarm K1
± 90,000,000 l/h /
0 to 100 °C
5000 l/h /
100 °C
K1 delay
Determines the delay time of
relay K1
0 to 100 s 0 s
K2 Switch Defines the type of output NC / NO NO
K2 Fn
Determines the function of
output K2
OFF
Q min
Q max
Q min/max
T min
T max
T min / max
TQ1 min
TQ1 max
TQ1 min / max
TQ2 min
TQ2 max
TQ2 min / max
Direction
Warning
OFF
AlarmMinK2 Value for the min. alarm K2
± 90,000,000 l/h /
0 to 100 °C
0 l/h /
0 °C
AlarmMaxK2 Value for the max. alarm K2
± 90,000,000 l/h /
0 to 100 °C
5000 l/h /
100 °C
K2 delay
Determines the delay time of
relay K2
0 to 100 s 0 s
K3 Switch Defines the type of output NC / NO NO
K3 Fn
Determines the function of
output K3
OFF
Q min
Q max
Q min/max
T min
T max
T min / max
TQ1 min
TQ1 max
TQ1 min / max
TQ2 min
TQ2 max
TQ2 min / max
Direction
Warning
Pulse
OFF
AlarmMinK3 Value for the min. alarm K3
± 90,000,000 l/h /
0 to 100 °C
0 l/h /
0 °C
AlarmMaxK3 Value for the max. alarm K3
± 90,000,000 l/h /
0 to 100 °C
5000 l/h /
0 °C
K3 delay
Determines the delay time of
relay K3
0 to 100 s 0 s