EasyManuals Logo

Generac Power Systems 6103 EcoGen User Manual

Generac Power Systems 6103 EcoGen
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
Fuel Conversion/Gas Connections
Installation Guidelines for Air-Cooled Generators 21
4. When measuring pipe length, add 2.5 feet (0.76m) for each angle or bend in the pipe run and add that to the
overall pipe distance.
5.4.1— Natural Gas Pipe Sizing
The following table indicates the maximum length (measured in feet / meters) allowed for various pipe sizes. The pipe
sizes are measured by inside diameter (ID) to include any fittings, valves (must be full flow), elbows, tees or angles.
Add 2.5 feet (0.76 m) to the overall distance for each bend, tee or angle in the pipe run.
NOTE: Tables based on Schedule 40 black pipe.
5.4.2— LP Vapor Pipe Sizing
The table indicates the maximum length (measured in feet / meters) allowed for various pipe sizes. The pipe sizes are
measured by inside diameter (ID) to include any fittings, valves (must be full flow), elbows, tees or angles. Add 2.5 feet
(0.76 m) to the overall distance for each bend, tee or angle in the pipe run.
NOTE: Pipe sizes are using a second stage regulator.
Allowable Pipe Distances (feet / meters)
Pipe Size
(in. / mm)
1 / 25 1.25 / 32 1.5 / 38
15 kW EcoGen
20 / 6 100 / 30 200 / 60
For 5-7 inches of water column (9-13 mm of mercury).
Allowable Pipe Distances (feet / meters)
Pipe Size
(in. / mm)
1 / 25 1.25 / 32 1.5 / 38
15 kW EcoGen
10 / 3 60 / 18 125 / 38
For pressures 3.5 - 5 inches of water column (7 - 9 mm of mercury).
Allowable Pipe Distances (feet / meters)
Pipe Size
(in. / mm)
0.75 / 19 1 / 25 1.25 / 32
15 kW EcoGen
250 / 76 70 / 21 350 / 106

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Generac Power Systems 6103 EcoGen and is the answer not in the manual?

Generac Power Systems 6103 EcoGen Specifications

General IconGeneral
BrandGenerac Power Systems
Model6103 EcoGen
CategoryInverter
LanguageEnglish

Related product manuals