Maintenance
Owner’s Manual for Stationary Diesel Generators 31
Figure 5-6. Generator Control Panel
30 Hour Break-In
Perform the following task:
• Replace Lubricating Oil and Oil Filter
NOTE: See Replace Lubricating Oil and Oil Filter
under Schedule B Maintenance.
Daily Maintenance (If Running
Continuously)
Perform the following tasks:
• Check Fuel Level and Fill
• Drain Fuel Filter
• Check Fuel Lines and Hoses
• Check Coolant Level
• Check Coolant Hoses
• Check Radiator for Clogging
• Check Lubricating Oil Level
NOTE: See Preliminary Instructions through Check
Lubricating Oil Level under Schedule A Maintenance.
Schedule A Maintenance
NOTE: Perform Schedule A maintenance once each
year or after 125 hours of service, whichever comes first.
Preliminary Instructions
1. See Remove From Service.
2. Remove access panels at the front and both sides
of the enclosure. See Access Panels.
3. Remove negative battery cable (black) from
negative (-) battery terminal.
NOTE: For general location of components, see
Component Locations.
Check Fuel Level and Fill
1. Observe fuel gauge to note level of fuel in tank.
See Figure 5-7.
2. Remove fuel fill cap from filler pipe.
3. Add fuel until needle on fuel gauge approaches the
F(ull) mark.
4. Install fuel fill cap onto filler pipe.
Figure 5-7. Check Fuel Level Gauge and Fill