www.generalclimate.com 26 Wall-Mounted Split Type
Anti frozen at cooling mode
10.4 Protection
10.4.1 3 minutes delay at restart for compressor.
10.4.2 Sensor protection at open circuit and breaking disconnection
10.4.3 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or too low(lower than
400RPM), the unit stops and LED displays failure information and can’t returns to normal operation automatically.
10.4.4 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED displays
failure information and can’t returns to normal operation automatically.
10.4.5 The current protection of the compressor
If compressor turns off for continuously 4 times due to current protection in 5 minutes from Compressor On, the unit stops and
LED displays failure information and cant returns to normal operation automatically.
10.5 Fan-only mode
Fan speed is high/mid/low/ Auto
10.6 Cooling mode
The 4-way valve is closed at cooling mode.
The action of the compressor and the outdoor fan:(T=indoor temperature)