www.generalclimate.com 28 Wall-Mounted Split Type
10.7.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the
same as that of cooling mode.
10.7.5 At dehumidifying mode, the action of fans of indoor is the same as that of air-only mode.
10.8 Heating mode
10.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode.
4-way valve must delay 2 minutes compared with compressor if the compressor changed
into non-heating mode or turned off. 4-way valve doesn't delay in dehumidifying mode
10.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating
mode, except for the defrosting mode or the end of defrost
10.8.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for
7 minutes after starting and then judge temperature. Meanwhile other protections are still
valid.
* This parameter can be changed from 0 to 3
10.8.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind function prevails.
Anti-cold wind control function at heating mode (T=indoor exchanger temp.)
10.8.5 Auto wind at heating mode (T=indoor temp.)