CONTROLS
BUZZER SILENCE
The occurrence of any new fire or fault condition will initiate the operation of the internal buzzer. By pressing this switch, the
operation of the buzzer will be stopped until a new fire or fault appears on the system.
SYSTEM RESET
Soft resets the entire system. A soft reset should be satisfactory under almost all circumstances, however a Master Reset
can be performed by cycling the power on the Panel (removing both primary AC and secondary DC supplies).
NOTE:
If an alarm has been detected, it is necessary to silence the alarms using SOUNDER SILENCE
before the SYSTEM RESET button will operate.
LAMP TEST
General User Access (no code entry required). Lights all the LEDS, turns on the LCD back light and sets all display pixels to
black. Lamp test only operates whilst the key is depressed.
SOUNDERS ACTIVATE / SILENCE
Activates all sounders. A second press deactivates all sounders. The adjacent LED is ON whilst the sounders are activated.
It is possible to define if pressing the SOUND ALARMS button will activate the systems Fire I/O's.
DISABLEMENTS
AUXILIARY RELAYS
When this button is activated all relays and I/O modules connected to the system have their outputs disabled. This includes
the normally energized FAULT relay, the FAULT I/O group and all ALARM I/O groups. When these outputs are disabled the
button LED is ON. Pressing the button again restores normal relay and I/O module operation.
NOTE:
IF I/O'S ARE TO BE ACTIVATED BY EVAC. CONDITION, THIS WILL OVERRIDE THE
DISABLEMENT.
SOUNDERS DISABLE
When this button is activated, all sounders will be disabled and the LED will be lit. Pressing it again will re-enable the
sounders and the LED will turn off.
SELECTED DETECTORS
Via the programming menus, individual sensors may have selective disablement turned on. When this button is activated,
those sensors that have selective disablement turned on will not generate a fire alarm condition. When activated, the
adjacent LED is ON.
If no devices have selective disablement turned on, then pressing this button will have no effect.
Pressing the button again restores normal sensor operation.
DELAYS ACTIVE
Only when this button is active (and the adjacent LED ON), Sounders and I/Os delays will operate.
Pressing the button again will deactivate the delays and will result in immediate sounder and I/O operation.
Under any fire condition the delays will be activated. If during the course of these delays this button is pressed, the delays
will be overridden and the sounders, together with any other fire indicating equipment, will be activated.