Voltage
Primary supply voltage 90 - 264V A.C.
EMC Standard EN55022 class B
EN61000-4-2,3,4,5,6,8,11
EN61000-3-2,3
Current
2.3 A PSU’s recommended for 1 to 4 loop panels.
The maximum alarm sounder current is 500 mA for each conventional sounder circuits.
The maximum quiescent current per loop is 150 mA.
The loop short circuit (trip) current is 900 mA.
Battery
Internal maximum 24 V / 7 AH
6