BATTERY REQUIREMENTS
The battery AH required are calculated from the following formula:
Quiescent current in mA of
the panel with everything
connected
Standby time required in
hours divided by 1000
Alarm current in Amps
(sounder load)
Round up to the next available battery size.
Quiescent currents for individual equipments are listed below:
24 V auxiliary outputs (2 OFF)
Refer to connected devices
NOTE:
In 2 to 4 loop panels use 7 AH batteries.
Example: A given installation has a single loop panel with 58 mA detector load, 1.4 A sounder load (including loop
sounders) and a 24 hour standby requirement.
Quiescent current in mA
of the panel with
everything connected
Standby time
required in hours
divided by 1000
Alarm current
in Amps
(sounder load)
65 (GEKKO)
+
58 (detector load)
24
(standby in hrs)
divided by 1000
85 (GEKKO)
+
58 (detector load)
=
143 mA +1.4 A
(sounder load)
=
= 3,724 AH +20% (0,722 AH) = 4,446 AH
The next available battery size is 5 AH