The default is FIRE reporting.
When the device is activated or reaches its alarm threshold, then the event is reported in accordance with this setting.
FAULT - Primarily intended for use with Input modules, it can allow activation of one input to trigger a fault report rather
than a fire.
PRE-ALARM - Sends warning when the level reported from a detector is 10 below the Alarm threshold. Used for early
warning in sensitive applications.
TRANSPARENT Configuration is ONLY applied to Input/Output or Input units. It is not compliant to EN54.
6-1-5 Set Immediate Evacuate for Device
When a detector set to immediate evacuate reports a fire, all Sounder Group settings are ignored. All sounders are operated
immediately as if the Sounder Configuration was set to PRESET and all delays are ignored.
6-1-6 Device Activation Overrides Delays
Allows a detector to be set to override all zonal and global sounder and I/O delay timers. When this device is activated the
Sounder Groups and I/O Groups associated with this device are also activated immediately (even if they were already
queued for delayed activation).
However this device will not start any of the timers either, which means that subsequent fires reported from other
detectors may experience the full delay duration (as programmed).
6-1-7 Inhibit Auxiliary Relays
Allows a specific detector to be set to not operate system I/O's and Auxiliary Relays when it reports a fire (Equivalent to
pressing auxiliary relays disablement button).
6-1-8 Global Behaviour Set-up
This function selects the Behaviour of all the detectors that have been set to GLOBAL.
Different settings can be entered for weekdays and for Saturday and Sunday.
Settings are:
Smoke only
Smoke / Heat
Heat only
TIMED
If TIMED is selected then the night and day behaviour settings used based on whether it is night or day.
Set the night and day behaviour using programming function 6-1-9. Define the start time of day and night using
programming function 8-1-2.
The Pre-alarm levels are always 10 below the alarm thresholds.
Ensure that the system clock, date and time are set correctly (function 8-1-1).
Note that in order to keep day/night and day settings consistent, a day setting starts at sunrise (which is set by function 8-
1-2). This means that, for example, the Saturday setting will start at 8:00 AM on Saturday.
6-1-9 Configure Timed Behaviour
Allows the Behaviour to be set for day and night.
Settings are:
Smoke only
Smoke / Heat
Heat only
NOTE:
Only detectors that have their Behaviour selected will have their settings changed,
and only if 6-1-8 Global Behaviour Set-up has been set to TIMED.
6-3 Device Specific - Functions only available for panels programmed to ZEOS Protocol
Analogue Loop device settings that are specific to devices that support the ZEOS communication protocol.
6-3-1 Select Device Behaviour Mode
Allows a specific operating mode to be selected for a specific device. Refer to the device manual for the mode definitions.
The modes usually relate to sensitivity or detection method.
Settings are:
Smoke Only
Smoke / Heat
Heat only
GLOBAL