8-1-5 Device Starts Evacuate Timer
Allows you to specify which detectors will start the Evacuate Timer.
The Evacuate Timer must be in DEVICE MODE to be activated by specific devices. See programming function 8-1-4.
8-1-7 Configure Extended Delays
This functionality enables the possibility of having a 2nd stage delayed operation of programmed Sounders and I/O’s in a
way that after acknowledgement of reported alarm before 1st stage, programmed delays are extended so that a local
inspection can take place.
● Extended delay ‘time of inspection’ delay is programmed.
● “Time of acknowledgement” delay is normally configured to sounders, I/O’s or both in functions 4-6 and/or 5-7.
● In case of a Fire Alarm, if “Alarm Silence” key is not pressed before 1st stage delay is elapsed, programmed sounders
and I/O’s will be activated.
● If “Alarm Silence” is pressed within 1st stage timer, 2nd stage delay starts. Alarm silence key LED blinks while the delay
is running until time is elapsed (activation) or a second press of “Alarm Silence” key.
● If “Alarm Silence” key is pressed a second timer, sounder activation is canceled but programmed I/O’s will be activated.
● I/O’s activation is only canceled with panel reset.
8-1-8 Configure Disablement Timer
This menu configures a timer to automatically re-enable all disablements after a selected time. It will show the running timer
countdown after a disablement has been set. To extend the countdown timer press the
▶ key.
NOTE:
The “Selective Disablements” are not affected by this.
8-2 Special Features Set-up
Programming functions associated with the system response and detection of a fire.
8-2-1 Two Devices to Evacuate
Enables or disables a system wide setting so that detection of fire by two detectors automatically starts evacuation.
Evacuation means any Sounder Group settings will be ignored and all sounders will be operated immediately.
8-2-2 Call Points to Evacuate
Enables or disables a system wide setting so that a report of fire from a call-point automatically starts evacuation.
Evacuation means any Sounder Group settings will be ignored and all sounders will be operated immediately.
8-3 Memory - BEWARE, ENGINEERS ONLY
Programming functions that are associated with management of the Panel memory.
There are three main memory sections on the panel. The following table shows an overview on the most relevant data per
memory section.