8-4-6 Select language
Allows the language setting for the system to be set.
Do this carefully, you will need to navigate back to this function to change it back again.
All text in the system will be changed to use the selected language. The change will take effect when ENTER is pressed.
8-4-8 Set Installer Access Code
This function allows changing the Installer Code without requiring knowledge of the Factory Code.
Display will show:
ENTER PRESENT CODE
ENTER NEW CODE
CONFIRM NEW CODE
8-4-9 Set Master Access Code
This function allows changing the Master Code without requiring knowledge of the Factory Code.
Display will show:
ENTER NEW CODE
CONFIRM NEW CODE
8-5 Network Configuration
All related with Network configurations and Network Protocols
8-5-1 Configure Panel Number
This function allows changing the Panel Network Number (address)
This should be unique in the network.
NOTE:
The Chameleon Rep will need to set an unique Panel Network Number
8-5-2 Known Panels
This function will show how many panels are being recognized and all panel network addresses detected. It will also indicate
its own Address on the network.
NOTE:
This function will only show the panels that are being listened (RX). Meaning that this will only
evaluate the receiving transmission path. For further troubleshoot info, please refer to Chameleon
Communications manual.
8-5-3 Installation Status
This function will show the status of the network and error messages.
Example: “No nodes detected”.
8-5-4 Broadcast Configuration
This function will send the local configuration to all panels in the system.
NOTE:
Before running this configuration, ensure that the latest configuration is already uploaded
into this panel.
Before running this function, please go to each panel in the network and run on each one the 8-5-2
menu and verify that all panels are “seeing” each other and there are no communication issues.
Do not unplug the power during Broadcast.
Do not run this function if you have network issues.
Ensure that the firmware is the same in all panels.
8-5-5 Communication Channels
This function shows in which channels data is being received.
If the panel has previously received data on a specific channel and no longer listens to messages, meaning that the channel
lost the receiving data, then it will signal (ERR).