EasyManua.ls Logo

Gree DC Inverter Multi VRF

Gree DC Inverter Multi VRF
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DC INVERTER MULTI VRF INSTALLATION
171
8.5 Requirements of Heat Insulation
¾ Heat Insulation Materials
The thermal insulation material of obturator foam shall be used. Fireproof level: B1.
The thermal conductivity shall not be higher than 0.035w/ (m·k) when the average
temperature is 0
.
¾ Thickness of thermal insulation layer
The thickness of thermal insulation layer on condensate pipe shall be over 10mm.
¾ The joint of thermal insulation materials must be adhered by using special glue and then
wrapped with plastic tape having a width not less than 5cm to avoid condensing.
¾ Thermal insulation is not required for the outdoor section of condensate pipe.

Table of Contents

Related product manuals