DC INVERTER MULTI VRF PRODUCT
37
Model GMV(L)-R112Zd/Na-K GMV(L)-R125Zd/Na-K
kW 11.2 12.5
Cooling Capacity
Btu 38216 42652
kW 12.5 13.5
Heating Capacity
Btu 42652 46064
m3/h 2200 2300
Air Flow Rate
CFM 1295 1354
Sound Pressure Level (H/L) dB(A) 54/- 55/-
External Static Pressure Pa 0 0
Power Supply
220-240V~50Hz 220-240V~50Hz
Output kW 0.18 0.18
Fan Motor
Running Current A 1.8 1.8
mm Φ15.9 Φ15.9
Gas Pipe
inch
5/8" 5/8"
mm Φ9.52 Φ9.52
Liquid Pipe
inch
3/8" 3/8"
Connecting
Pipes
Connection Method Flare Connection Flare Connection
Drain Pipes
(External Dia. × Thickness)
mm Φ17×1.75 Φ17×1.75
Unit Dimensions
(W×D×H)
mm 1590×238×695 1590×238×695
Package Dimensions
(W×D×H)
mm 1714×330×830 1714×330×830
Weight(Net/Gross)
kg 44/53 44/53
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
4.3 Operation Range
Model Range of outdoor temperature ( )℃℉
Cooling
10℃(50℉)~48℃(118.4℉)
Heating
-20℃(-4℉)~27℃(8℉)