DC INVERTER MULTI VRF MAINTENANCE
180
F4
Outdoor
ambient
temperature
sensor error
Outdoor
environment
sensor
Test for 30 seconds successively to check if the temperature
sensor is disconnected. If yes, alarm will be sent; otherwise no
processing will be made. If the controller of outdoor unit detects
failure of outdoor sensor under open circuit, short circuit and
excess of test value, the outdoor unit will execute the following
default actions, that is, the error message will be sent to each
indoor unit and the error code will be displayed via error indicator
or wired controller. When the outdoor ambient temperature is
lower than -5
, the disconnection failure of outdoor inlet, middle
and exit sensors in shield room will be processed as under -30
.
F7
Outdoor defrost
temperature
sensor error
Outdoor
Defrost Sensor
Test for 30 seconds successively to check if the temperature
sensor is disconnected. If yes, alarm will be sent; otherwise no
processing will be made. If the controller of outdoor unit detects
failure of outdoor sensor under open circuit, short circuit and
excess of test value, the outdoor unit will execute the following
default actions, that is, the error message will be sent to each
indoor unit and the error code will be displayed via error indicator
or wired controller. When the outdoor ambient temperature is
lower than -5
, the disconnection failure of outdoor inlet, middle
and exit sensors in shield room will be processed as under -30
.
F9
Exhaust
temperature
sensor error
Exhaust
temperature
sensor
Test for 30 seconds successively to check if the temperature
sensor is disconnected. If yes, alarm will be sent; otherwise no
processing will be made. If the controller of outdoor unit detects
failure of outdoor sensor under open circuit, short circuit and
excess of test value, the outdoor unit will execute the following
default actions, that is, the error message will be sent to each
indoor unit and the error code will be displayed via error indicator
or wired controller. When the outdoor ambient temperature is
lower than -5
, the disconnection failure of outdoor inlet, middle
and exit sensors in shield room will be processed as under -30
.
Error Code of Duct-type Unit
Error
Error
Code
Error
Error
Code
Prevention against low
temperature
E2
Error with oil temperature
sensor 2 (digital)
Fb
Outdoor ambient temperature
sensor error
F4
Indoor ambient temperature
sensor error
F0
Indoor tube-inlet sensor error F5 Exhaust overtemperature E4
Outdoor tube-middle sensor error F6 Low-pressure protection E3
Outdoor tube-exit sensor error F7 Overcurrent Protection E5
Error with exhaust temperature
sensor 1 (fixed-frequency)
F8 High-pressure protection E1
Indoor tube-inlet sensor error F1 Communication error E6
Indoor tube-middle sensor error F2 High-pressure valve error Fc
Indoor tube-exit sensor error F3 Low-pressure valve error Fd
Error with exhaust temperature
sensor 2 (fixed-frequency)
F9
Water-full protection
(Cassette)
Eb
Error with oil temperature sensor
1 (fixed-frequency)
FA
King Series
Error
Tube-inl
et
sensor
error
Tube-mid
dle sensor
error
Tube-exit
sensor
error
Room
sensor
error
Defro
st
Antif
reez
e
Mode
confli
ct
Com
muni
catio
n
error
Outdo
or unit
failure
Power
Lamp
Bright Bright Bright Bright
Brigh
t
Dark Dark Blink Blink
Tes t
lamp
Dark Blink Blink Bright Blink Dark Blink Blink Dark
Timer
lamp
Blink Blink Bright Blink Dark Blink Bright Blink Dark

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree DC Inverter Multi VRF and is the answer not in the manual?

Gree DC Inverter Multi VRF Specifications

General IconGeneral
BrandGree
ModelDC Inverter Multi VRF
CategoryAir Conditioner
LanguageEnglish

Related product manuals