DC INVERTER MULTI VRF MAINTENANCE
187
Overcurrent occurs in operation, i.e. the indicator will display the current protection just after startup.
Check the indoor units for
matching
Within 135%
Correct the match of indoor units to
allowable capacity
Check if the charge volume is
too high
The charge volume is
too high
A
djust to allowable range stated
in the specifications
Use DC level to monitor P & N
voltage of the module
Voltage stabilized 252-330V, with
no fluctuation over 10V
DC capacitor damaged.
Replace it
Compressor damaged; module
damaged