DC INVERTER MULTI VRF PRODUCT
18
Model GMV(L)-R22P/NaB-K GMV(L)-R28P/NaB-K GMV(L)-R36P/NaB-K
kW 2.2 2.8 3.6
Cooling Capacity
Btu 7507 9554 12284
kW 2.5 3.2 4.0
Heating Capacity
Btu 8530 10918 13648
m3/h 450 570 570
Air Flow Rate
CFM 265 335 336
Sound Pressure Level (H/L) dB(A) 37/33 39/35 39/35
External Static Pressure Pa 50/20 50/20 50/20
Power Supply
220-240V~50Hz 220-240V~50Hz 220-240V~50Hz
Output kW 0.04 0.06 0.06
Fan Motor
Running Current A 028 0.41 0.41
mm
φ9.52 φ9.52 φ12.7
Gas Pipe
inch
3/8" 3/8" 1/2"
mm
φ6.35 φ6.35 φ6.35
Liquid Pipe
inch
1/4" 1/4" 1/4"
Connecting
Pipes
Connection Method Flare Connection Flare Connection Flare Connection
Drain Pipes
(External Dia. × Thickness)
mm
φ20×1.5 φ20×1.5 φ20×1.5
Unit Dimensions
(W×D×H)
mm 880×655×250 880×655×250 880×655×250
Package Dimensions
(W×D×H)
mm 1020×745×305 1020×745×305 1020×745×305
Weight(Net/Gross)
kg 27/31 28.5/33.5 28.5/33.5
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level is tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.