DC INVERTER MULTI VRF                                                            MAINTENANCE 
  218
z
  Ultra-thin Duct-Type Unit 
Removal and Assembly of Fan Motor 
Remarks: Before removing the fan, make sure to cut off the power firstly. 
Step Illustration Handling Instruction 
1. Unplug the 
motor cables
 
 
●
Cut off the power supply 
of indoor unit. Use 
screwdriver to remove the 
electric box cover and 
unplug the motor cables 
in electric box.
 
2. Remove the 
back propeller 
housing
 
 
●Loosen the clamp 
between back propeller 
housing and front 
propeller housing. 
Remove the back 
propeller housing
 
3. Remove the 
front propeller 
housing
 
 
●Use screwdriver to 
loosen the screws fixing 
the front propeller 
housing. Remove the 
front propeller housing.
 
4. Loosen the fan 
and motor.
 
 
●
Use inner hexagonal 
spanner to loosen the 
screws on fan and 
remove the clamp fixing 
the motor.
 
5. Remove the 
motor
 
 
●
Firstly, disengage the 
motor from motor support 
and then disengage the 
fan from the motor. Then, 
remove the motor from 
the lower return air inlet 
frame. In which, for the 
motor with automatic 
motor support, the motor 
support shall be removed 
in advance and then 
changed to the unit.
 
6. Replace with a 
new motor
 
 
●
Assemble the unit in 
reverse to the 
disassembly procedures 
and energize it for testing.