DC INVERTER MULTI VRF MAINTENANCE
z Duct-Type Unit5.6 kW8.0 kW
Removal and Assembly of Fan Motor
Remarks: Before removing the fan, make sure to cut off the power firstly.
Step Illustration Handling Instruction
1. Unplug the motor
cables
Cut off the power
supply of indoor unit.
Use screwdriver to
remove the electric
box cover and unplug
the motor cables in
electric box.
2. Remove the filter
sub-assembly and
return air inlet cover
board
Remove the filter
sub-assembly from the
return air inlet frame
and use screwdriver to
remove the return air
inlet cover board.
3. Remove the screws
on fan sub-assembly.
Remove the screws
on fan sub-assembly.
4. Overturn the
propeller housing
Rotate the propeller
housing to the return
air inlet opening
according to arrow
direction.
5. Loosen the fan and
motor.
Use inner hexagonal
spanner to loosen the
screws on fan and
remove the clamp
fixing the motor.