DC INVERTER MULTI VRF                                                                  PRODUCT 
  27
Model GMV(L)-R71T/Na-K GMV(L)-R80T/Na-K GMV(L)-R90T/Na-K
kW 7.1  8.0  9.0 
Cooling Capacity 
Btu 24230  27300  30700 
kW 8.0  8.8  10.0 
Heating Capacity 
Btu 27300  30030  34120 
m3/h 1180  1180  1860 
Air Flow Rate 
CFM 695  695  1095 
Sound Pressure Level (H/L)  dB(A)  39/35  39/35  40/36 
External Static Pressure  Pa  0  0  0 
Power Supply 
220-240V~50Hz 220-240V~50Hz 220-240V~50Hz 
Output kW  0.035  0.035  0.06 
Fan Motor 
Running 
Current 
A 0.37  0.37  0.59 
mm  Φ15.9  Φ15.9  Φ15.9 
Gas Pipe 
inch 
5/8" 5/8" 5/8" 
mm  Φ9.52  Φ9.52  Φ9.52 
Liquid Pipe 
inch 
3/8" 3/8" 3/8" 
Connecting 
Pipes 
Connection Method  Flare Connection  Flare Connection  Flare Connection 
Drain Pipes 
(External Dia. × Thickness) 
mm 
Φ30×1.5  Φ30×1.5  Φ30×1.5 
Unit Dimensions 
(W×D×H) 
mm 
Main body:840×840×240 
Panel:950×950×60 
Main body:840×
840×320 
Panel:950×950×60
Package Dimensions 
(W×D×H) 
mm 
Main body:960×960×310 
Panel:1040×1025×115 
Main body:960×
960×394 
Panel:1040×1025
×115 
Net Weight 
(Main body/Panel) 
kg 30/6.5  38/6.5 
Gross Weight 
(Main body/Panel) 
kg 38/10  46/10 
 
Notes: 
①  Refer to the product nameplate for parameters and specification of the unit; 
②  The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only 
units dose not have any parameters of performing heating; 
③  The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in 
actual operation.