DC INVERTER MULTI VRF PRODUCT
29
Model GMV(L)-R125T/Na-K GMV(L)-R140T/Na-K
kW 12.5 14.0
Cooling Capacity
Btu 42650 47770
kW 13.5 14.5
Heating Capacity
Btu 46062 49470
m3/h 1860 1860
Air Flow Rate
CFM 1095 1095
Sound Pressure Level (H/L) dB(A) 40/36 40/36
External Static Pressure Pa 0 0
Power Supply
220-240V~50Hz 220-240V~50Hz
Output kW 0.06 0.06
Fan Motor
Running
Current
A 0.59 0.59
mm Φ15.9 Φ15.9
Gas Pipe
inch
5/8" 5/8"
mm Φ9.52 Φ9.52
Liquid Pipe
inch
3/8" 3/8"
Connecting
Pipes
Connection Method Flare Connection Flare Connection
Drain Pipes
(External Dia. × Thickness)
mm
Φ30×1.5 Φ30×1.5
Unit Dimensions
(W×D×H)
mm
Main body:840×840×320
Panel:950×950×60
Package Dimensions
(W×D×H)
mm
Main body:960×960×394
Panel:1040×1025×115
Net Weight
(Main body/Panel)
kg 38/6.5
Gross Weight
(Main body/Panel)
kg 46/10
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.