DC INVERTER MULTI VRF PRODUCT
33
Model GMV(L)-R22G/NaC-K GMV(L)-R28G/NaC-K GMV(L)-R36G/NaC-K
kW 2.2 2.8 3.6
Cooling Capacity
Btu 7507 9554 12284
kW 2.5 3.2 4.0
Heating Capacity
Btu 8530 10919 13649
m3/h 360 360 500
Air Flow Rate
CFM 212 212 294
Sound Pressure Level
(H/L)
dB(A) 37/28 37/28 43/28
External Static Pressure Pa 0 0 0
Power Supply 220-240V~50Hz 220-240V~50Hz 220-240V~50Hz
Output kW 0.014 0.014 0.022
Fan Motor
Running
Current
A 0.15 0.15 0.22
mm Φ9.52 Φ9.52 Φ12.7
Gas Pipe
inch
3/8" 3/8" 1/2"
mm Φ6.35 Φ6.35 Φ6.35
Liquid
Pipe
inch
1/4" 1/4" 1/4"
Connecting
Pipes
Connection Method Flare Connection Flare Connection Flare Connection
Drain Pipes
(External Dia. ×
Thickness)
mm
φ20×1.5 φ20×1.5 φ20×1.5
Unit Dimensions
(W×D×H)
mm
770×190×250 770×190×250 830×189×285
Package Dimensions
(W×D×H)
mm
955×330×272 955×272×330 1006×395×295
Weight(Net/Gross)
kg 8/14.3 8/14.3 11/15.8
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.