DC INVERTER MULTI VRF CONTROL
47
Outdoor dry bulb temperature ()
Or the outdoor ambient temperature is below -6 ; and keeps heating (the four-way valve is under the heating
position) for 2 hours;
Defrosting Stop Conditions:
Outdoor coil pipe temperature is higher than 15 or the defrosting is running for 10 minutes continuously.
Defrosting Movements:
The defrosting is made by switching four-way valve to cooling mode.
The action time for unit defrosting operation is shown as the following figure.
Timing diagram of the defrosting process
Intermediate sensor temperature ()