DC INVERTER MULTI VRF CONTROL
51
一分钟内未达到阀值
8
s
60s
高风档
风机关
设定风速
0
t
蒸发器
t
蒸发器
v
T
蒸
/ts
/tC
。
Once the indoor unit started under heating operation, if the fan stops in any case (including starting up,
defrosting, fault, no capability needs), the anti cold air operation will keep before starting the fan for the next time.
Once the indoor fan is started, unless the fan stops, the anti cold air operation will not take effect even t
evaporator
< T
v-evaporator
again.
◆ Blowing Residual Heat Operation
When the indoor unit runs under heating mode, if it should be stopped for reaching the temperature spot, fault,
defrosting etc., you should carry on the blowing residual heat operation before stop, in order to exclude the inner
surplus heat of evaporator and electric heater.
When the indoor unit needs to carry out blowing residual heat operation, the indoor fan should be switch to low
fan speed, and turn off the indoor fan after running the corresponding period T
residual heat
. Show as the following
figure:
/ts
0
设定风速
低风档
风机关
T
余热
不需要吹余热
需要吹余热
The corresponding residual heat removal period for different models in different situations is listed in the
following table.
The blowing period for residual heat in different situations T
residual heat
(s)
Model Stop
Reaching the
temperature
point
Entering into
the defrosting
Malfunction
stop
Duct Type Series 100 60-100 60 60
Wall Mounting
Type Series
50 10-50 10 10
Cassette Type
Series
60
Low wind,
non-stop
20 20
Special case: For the indoor units of cassette series, it will run at low fan speed when it reaches the temperature
point, and do not need to stop the fan.
3) Compensation for Heating Temperature
Under the standard conditions, when the air conditioner is running, the units will regulate the capacity output of
indoor unit according to its setting temperature and air inlet temperature, and in order regulate the indoor
temperature to the set temperature. When the air conditioner is installed too high and under the heating mode, the
hot air will easily gather up due to the density, so the temperature of living space may not reach the set
temperature, leading to uncomfortable feeling.
Therefore, you should use the temperature compensation function under heating mode: to reflect the real
temperature of living space by reducing 2 degrees of the air inlet temperature. You may keep comfortable
temperature in the living space. Shown as the following figure:
Necessary for blowing residual heat
Unnecessary for
blowing residual
heat
Low speed
Fan OFF
Setting wind speed
T
residual heat
High
Fan OFF
Setting speed
t
evaporator
t
evaporator
Failing to reach the valve value within one minute
Tv-evaporator