34
Multi VRF Indoor
Unit Service Manual
PRODUCT
Model GMV-R90Zd/Na-K GMV-R112Zd/Na-K GMV-R125Zd/Na-K
Product Code EM600N0040 EM600N0050 EM600N0020
Model GMVL-R90Zd/Na-K GMVL-R112Zd/Na-K GMVL-R125Zd/Na-K
Product Code EM600N0120 EM600N0130 EM600N0140
Cooling Capacity
kW 9.00 11.20 12.50
kBtu/h 30.71 38.21 42.65
Heating Capacity
kW 10.00 12.50 13.50
kBtu/h 34.00 43.00 46.00
Air Flow Rate
m
3
/h 2100 2200 2300
CFM 1236 1295 1354
ESP(standard/max./range) Pa 0 0 0
Sound Pressure Level dB(A) 51 54 55
Power Supply V/Hz/Ph 220-240/50/1 220-240/50/1 220-240/50/1
Fan Motor
Output kW
0.15 0.18 0.18
Running Current A 1.30 1.50 1.50
Connecting
Pipes
Gas Pipe
mm
inch
5/8 5/8 5/8
Liquid Pipe
mm
inch
3/8 3/8 3/8
Connection Method Flare Connection Flare Connection Flare Connection
Drain Pipes (External Dia.×Thickness) mm 28 ×3.0 28 ×3.0 28 ×3.0
Unit Dimensions (W×D×H) mm 1590 ×238 ×695 1590 ×238 ×695 1590 ×238 ×695
Package Dimensions (W×D×H) mm 1814 ×330 ×930 1814 ×330 ×930 1814 ×330 ×930
Net Weight kg 44.0 44.0 44.0
Gross Weight kg 53.0 53.0 53.0
Notes:
①.
The above performance parameter is measured according to the standard of GB/T 18837-2002.
②.
③.
The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the
cooling only units dose not have any parameters of performing heating.
④.
Above parameters are tested under the condition:high fan speed
Cooling : Indoor air temperature 27°C DB/19°C WB;
Heating : Indoor air temperature 20°C DB/15°C WB.
⑤ .
Location of microphone:
Indoor Side
Indoor Side
Ceiling Type
Microphone
Air outlet
1m
Floor
Type
Microphone
1m
1
m
1m