GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
184
Troubleshooting:
2.2.4.65 F9 Compressor 5 discharge temperature sensor error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
Sample the AD value of temperature sensors through temperature sensors circuit and judge the
range of AD value; if the sampled AD value exceeds upper limit and lower limit in 30 seconds
continuously, report the error.
Possible reason
■Poor contact between discharge temperature sensor and terminal in mainboard interface
Discharge temperature sensor is abnormal
Detecting circuit is abnormal