GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
196
Troubleshooting:
2.2.4.80 H6 Drive IPM module protection of fan
Error display:
ODU mainboard will display
Error judgment condition and method:
Check the error code on nixie tube of ODU main control board. If H6 is displayed, it indicates Drive
IPM module protection of fan
Possible reason
Poor contact of fan UVW wire
Fan is broken
Fan blade is blocked (Fan blade is blocked and motor shaft is rusty)
■Fan drive board is abnormal